9356 N. Keeler Ave.
Skokie, IL 60076


Inspection Report

Prepared For:
Louis Smartbuyer

Property Address:
524 S. Suburban Lane
South Suburbs, IL


Member - National Association of Certified Home Inspectors

_______________________________________________________

William J. Decker Jr. Illinois State License 050.0002240




Date: 4/10/2004 Time: 4:30 AM Report ID: Exp 3 Med
Property:
524 S. Suburban Lane
South Suburbs, IL
Customer:
Louis Smartbuyer
Real Estate Professional:

Subject property is a 15 year old (1991) split level house with attached 3 car garage.  The house sits facing the east and has a central, hipped roof, with two gables crossing it, to the south (over the garage) and to the north.  The back is equipped with a wooden deck, a portion of which is screen and metal siding enclosed.  It sits on a generally well graded lot and is located near the turnaround section of a cul-du-sac street.

Homes more than 5 years old may have areas that are not current in code requirements. This is not a new home and this home cannot be expected to meet current code standards.  While this inspection makes every effort to point out safety issues that may have arisen in the interim, it does not inspect for code but does point out any items that do not meet current safety standards. It is common that homes of any age will have had repairs performed and some repairs may not be in a workmanlike manner.  Some areas may appear less than standard. This inspection looks for items that are not functioning as intended.  It does not grade the repair.  It is sometimes common to see old plumbing or mixed materials.  Sometimes water signs in crawlspaces or basements could be years old from a problem that no longer exists.  Or, it may still need further attention and repair.  Determining this can be difficult in a lived in home.  Sometimes homes have signs of damage to wood from wood eating insects.  Having this is typical and fairly common.  If the home inspection reveals signs of damage you should have a qualified pest control company inspect further for activity and possible hidden damage.  Always consider hiring the appropriate expert for any repairs or further inspection.

 

Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be read and considered when evaluating this property.

Note:Any recommendations by the inspector to repair or replace or deal with a significantly deficient item suggests an evaluation by a licensed and insured contractor specifically qualified to determine the condition and safety of the described item, component or system.  Please note that Home Inspectors in the State of Illinois are required to note any safety hazards, whether they comply with older, obsolete local building codes or not.  Licensed and insured contractors are not.  Repairs done by persons other that licensed and insured contractors carry with them added liability for the customer.  All work done on the subject property should be accompanied by a copy of all invoices and warranties, such warranties should be transferable to the new owner and should include the contractor's license number and a copy of their insurance certification.

Category Definitions:

Inspected (IN) = The system, component or item was visually observed at a certain time and under certain conditions.

Not Inspected (NI)= The system, component or item was not inspected and no representations of whether or not it was functioning are intended.  The reason could be that the item was not connected (gas, water, electrical disconnected), obstructed, or not accessible.  In any case, the reason that the item, system or component was not inspected is stated in the comments.

Not Present (NP) = This system, component or item is not present in the subject property.

Watch List or Maintenance (WL) =Either the system, component or item needs regular maintenance to remain functioning in a proper manner and those maintenance processes are noted or the item should be watched in anticipation of future problems.

Repair or Replace (RR) = The item, component or unit is not functioning as intended or needs further inspection by a licensed and insured contractor. Most of these type of comments describe items that will lead to more serious problems if not addressed.  Items, components or systems that can be repaired to satisfactory condition may not need replacement.

Significantly Deficient (SD) = Defined by Illinois State Law as either a) not functioning or b) posing a safety hazard.  It should be noted that a large number of significantly deficient items can be addressed at little cost. It is important to remember that The safety of a significantly deficient item is not based upon mere local building codes, which contain 'grandfathering' clauses, or the common practices of tradesmen, but on national and international safety requirements and with the well being of the property and the client in mind.

Please Note:  If you have any questions or any thing is unclear, please do not hesitate to contact Decker Home Services and/or your specific inspector.  We are happy to answer any of your questions and have a large knowledge base of information and experienced, qualified expert NACHI instructors and inspectors from around the entire country at our disposal.  We consider it very important for you to fully and completely understand the condition of the subject property and will do all we can to help you in the process.

Age Of Home:
Over 10 Years (1991)

Client Is Present:
Yes

Realtors Present:
Buyer's Realtor

Weather:
Clear

Temperature:
85

Rain in last 3 days:
Yes

Radon Test:
No

Mold Test:
No

Water Test:
No




General Summary


9356 N. Keeler Ave.
Skokie, IL 60076

Customer
Louis Smartbuyer

Property Address
524 S. Suburban Lane
South Suburbs, IL

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or appear to warrant further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of the home. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

Structural Components
1.1 FOUNDATION - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend that the grade around the entire perimeter of the property be lowered to keep a minimum of 6" (for brick exterior houses) and 8" for siding or stucco exterior houses) of the foundation exposed to guard against water infiltration into the structure.
1.7 ROOF STRUCTURE AND ATTIC - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend that the water damaged OSB roof sheathing, located in the garage, northwest corner, be evaluated and repaired, along with the repair of the downspouts on the western side of the garage gable roof, proximate to the hip roof side, as needed, by a licensed and insured roofer.

Exterior
2.1 WALL CLADDING FLASHING AND TRIM - Findings
  Inspected, Watch List - Maintenance
 
1) WL - Recommend that exterior caulking, where two different exterior surfaces meet, around windows and doors and where slab porches meet exterior walls, be evaluated and repaired on an annual basis.  This is a regular maintenance item.

2) Wooden siding requires annual evaluation and minor repair of nail pops and flaws.  This is a normal maintenance item.

2.3 DOORS (Exterior) - Findings
  Inspected, Repair or Replace, Significantly Deficent
 
1) SD) Recommend that the exterior door between the garage and the living area be equipped with self closing spring type hinges to guard against infiltration or fire or noxious gasses from the garage to the living area.  This is a safety hazard.

2) RR - Recommend scraping, priming and painting of the door frame for the rear garage door.

2.5 WINDOWS (Exterior) - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend exterior wooden window frames be scrapped, primed and re-painted to avoid further deterioration.

2) RR - Recommend that the junction of the window metal cladding and the exterior brick be caulked to prevent water penetration.

2.7 GARAGE DOOR OPERATORS - Findings
  Inspected, Watch List - Maintenance, Repair or Replace
 
1) WL - Adjust resistance auto reverse feature on south garage door.

2) RR - Recommend that garage doors be scrapped, primed and painted.

3) WL - Recommend evaluation and adjustment of the overhead springs and cables for the garage doors.

2.9 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES AND APPLICABLE RAILINGS - Findings
  Inspected, Watch List - Maintenance, Repair or Replace
 
1) WL - Cracks between poured slab porches and exterior walls should be regularly checked and re-caulked, as needed, to guard against water infiltration.

2) RR - Wooden porches and decks should be supported by the required concrete footings.  All deck and porch steps should also be properly supported by concrete footings.  Recommend evaluation by a licensed and insured deck contractor.

3) SD - All deck railing ballaster should be spaced no further apart than 3 1/2" to guard against entanglement.  This is a safety hazard.

4) SD - Recommend evaluation of the master bedroom balcony by a licensed and insured general contractor.  It is the opinion of this inspector that it is not safe for use.

2.11 EAVES, SOFFITS AND FASCIAS - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend securing the fascia board on the gable peak of the south roof.
2.13 VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIOS, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building) - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend that the trees growing directly against the foundation on the south side be removed as a guard against foundation damage.

Roofing
3.1 ROOF COVERINGS - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend evaluation of damaged area of roof by a licensed and insured roofer.
3.3 FLASHINGS, SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend evaluation of the roof flashing to the wooden sided side walls and the chimney cap by a licensed and insured roofer.
3.4 ROOFING DRAINAGE SYSTEMS - Inspect and Describe
  Inspected
 
Roof is drained by means of metal gutters and downspouts.  The metal gutters display no signs of rust and only minor signs of physical damage.  The gutter hangers are spaced more than the recommended 18" apart (Picture 1).

The downspouts do not extend far enough away from the foundation to be effective in draining water away from the basement.

There are two downspouts, located on the garage roof and draining the south side of the upper hip roof, that drain directly on the roof and have already cause signs of past water infiltration (Picture 2, 3).

3.5 ROOFING DRAINAGE SYSTEMS - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend that the downspouts be extended to release drainage water at least 6' away from the structure's foundation.

2) RR - Recommend that all downspouts that drain an upper section of roof terminate either into a lower roof section gutter or to the ground, directly as a guard against excessive water buildup and accelerated roof failure.  Recommend evaluation and repair by a licensed and insured roofer.


Plumbing System
4.1 INTERIOR DRAIN, WASTE AND VENT SYSTEMS - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend evaluation the drain venting and noises from the master bathroom whirlpool tub by a licensed and insured plumber.
4.3 INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend installation of a new extunction on the 1st floor bathroom showerhead to guard against showerhead movement.
4.8 SUMP PUMP - Findings
  Inspected, Significantly Deficent
 
1) SD - Recommend that all water handling appliances, including sump pumps and water pressure pumps, be GFCI protected.  This is a safety hazard.  Also recommend that all sump pumps be equipped with battery backup so that their operation is assured during periods of electrical blackout. SD - Recommend that all water handling appliances, including sump pumps and water pressure pumps, be GFCI protected.  This is a safety hazard.  Also recommend that all sump pumps be equipped with battery backup so that their operation is assured during periods of electrical blackout.

Electrical System
5.3 BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend evaluation of the added wiring, located in the laundry utility room to determine the legality of its use by a licensed and insured electrician.
5.5 CONNECTED DEVICES AND FIXTURES - Findings
  Inspected, Significantly Deficent
 
1) RR - Recommend evaluation of the exterior outlet located near the front door by a licensed and insured electrician.  It was not powered.
5.7 GFCI, AFCI PROTECTION OF RECEPTACLES - Findings
  Inspected, Significantly Deficent
 
SD - Recommend GFCI (Ground Fault Circuit Interrupt) protected outlets, or GFCI circuit breakers for all outlets that are:
  • Over the counter in kitchens and anywhere in bathrooms.
  • Within 6' or any water source (sinks, bathtubs, bathroom basins)
  • Located in unfinished areas of basements.
  • In garages.
  • Powering garage door openers serving metal garage doors.
  • Serve water carrying appliances, such as dishwashers, in sink disposers, sump pumps, water supply boost pumps, sprinkler systems or clothes washers.
  • Located on the exterior of the house.
  • Around pools, spas or that power whirlpool type tubs.

Recommend  AFCI (Arc Fault Circuit Interrupt) protected outlets or circuit breakers be used for all branch wiring that services bedroom areas.

Recommend that all such installation be done by a licensed and insured electrical contractors and that these outlets and breakers be tested every month by means of the test buttons that they are equipped with.

5.9 SMOKE DETECTORS, CARBON MONOXIDE DETECTORS - Findings
  Inspected, Significantly Deficent
 
SD) - Recommend that smoke detectors be located:
  • In the hallways outside of bedrooms.
  • At the top and bottom of all stairways.
  • In the kitchen

Recommend that carbon monoxide detectors be located in all bedrooms and in any utility room containing a gas fired water heater, furnace or boiler.

Recommend that all smoke and carbon monoxide detectors be hard wired to the building's electrical system and be equipped with rechargeable battery backup.


Heating
6.1 HEATING EQUIPMENT - Findings
  Inspected, Significantly Deficent
 
1) SD - Recommend that the furnace be evaluated by a licensed and insured HVAC contractor to determine if the amount of combustion air is sufficient for proper furnace operation.  This is a safety concern.

2) SD - Recommend that the return duct vent, located to the east of the furnace, be covered over to avoid it robbing the furnace of combustion air.

6.4 CHIMNEYS, FLUES AND VENTS - Findings
  Inspected, Repair or Replace
 
1) Recommend that the furnace vent flue be covered with an appropriate vent termination by a licensed and insured HVAC technician.
6.6 HEAT DISTRIBUTION SYSTEMS - Findings
  Inspected, Watch List - Maintenance
 
1) WL - Recommend that the ductwork be cleaned by a licensed and insured duct cleaning contractor.
6.8 SOLID FUEL HEATING DEVICES - Findings
  Inspected, Watch List - Maintenance
 
1) WL - Recommend cleaning of the wood burning fireplace flue by a licensed and insured chimney sweep.

.

6.10 GAS/LP FIRELOGS, LOG LIGHTERS AND FIREPLACES - Findings
  Inspected, Significantly Deficent
 
1) SD - Gas log lighters are not equipped with automatic gas shut off valves or any safety features that will guard against gas infiltration into the house.  Without any safety feature, this inspector considers log lighters to be unsafe, especially in houses with small children.  Recommend evaluation by a licensed and insured fireplace contractor

Interiors
8.3 FLOORS - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend repair of the cracked floor tile in the entryway area.

2) RR - Recommend repair of the loose tile in the master bathroom.

3) Recommend re-caulking of the surround of the whirlpool tub to guard against water infiltration.

8.6 COUNTERS AND OF CABINETS - Findings
  Inspected, Watch List - Maintenance
 
1) WL - Suggest that replacement of kitchen countertops may be needed in a 2 to 3 year period due to delamination.
8.8 DOORS (Interior) - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend repair of the door handle for the 2nd floor hallway bathroom.
8.9 WINDOWS (Interior) - Inspect and Describe
  Inspected
 
All windows operated properly and had no signs of rot or physical damage.

Insulation and Ventilation
9.2 VENTING SYSTEMS (Kitchens, baths and laundry) - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend that all bathroom ceiling fan vents, kitchen vents and laundry dryer vents be vented to the exterior, directly, to guard against excessive moisture buildup and the possibility of mold formation.
9.4 VENTILATION, FANS AND THERMOSTATIC CONTROLS (ATTIC) - Findings
  Inspected, Repair or Replace
 
1) RR - Recommend that the wasp nests be removed from the roof vents over the garage.

Built-In Kitchen Appliances
10.0 DISHWASHER
  Inspected, Significantly Deficent
 
Dishwasher was a Tappen.  It did not operate at the time of the inspection.  Seller stated that the Dishwasher "need's servicing".

The dishwasher was not powered by means of a GFCI protected circuit.  GFCI outlets are recommended for all water carrying appliances as a safety feature.

10.1 RANGES/OVENS/COOKTOPS
  Inspected, Repair or Replace
 
Stove was operated.  It is equipped with electric spark ignition.

Oven is electric and appears to have convection and microwave capabilities, but only the oven function was operated.  Suggest client obtain the instruction manual.

10.2 RANGE HOOD
  Inspected, Repair or Replace
 
Operated.  Needs cleaning of the grease filter.
10.3 FOOD WASTE DISPOSER
  Inspected, Repair or Replace
 
Disposer was operated, but the switch controlling it appears to have an intermittent flaw, only operating the disposer sometimes.

Recommend replacement of switch operating the disposer, located to the right of the sink above the counter.



Prepared Using HomeGauge http://www.homegauge.com/ SHGI (c) 2000-2004 : Licensed To Decker Home Services, LLC.




Structural Components

The Home Inspector shall observe structural components including foundations, floors, walls, columns or piers, ceilings and roof. The home inspector shall describe the type of Foundation, floor structure, wall structure, columns or piers, ceiling structure, roof structure. The home inspector shall: Probe structural components where deterioration is suspected; Enter under floor crawl spaces, basements, and attic spaces except when access is obstructed, when entry could damage the property, or when dangerous or adverse situations are suspected; Report the methods used to observe under floor crawl spaces and attics; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to: Enter any area or perform any procedure that may damage the property or its components or be dangerous to or adversely effect the health of the home inspector or other persons.

Styles & Materials
FOUNDATION:
POURED CONCRETE
FRAMING METHOD:
PLATFORM
FLOOR STRUCTURE:
2 X 8
WALL STRUCTURE:
2 X 4 WOOD
CEILING STRUCTURE:
2 x 8 WOODEN JOISTS
BEAMS COLUMNS OR PIERS:
STEEL GIRDER
STEEL COLUMNS
CEILING STRUCTURE:
2X8
ROOF STRUCTURE:
STICK-BUILT
2 X 6 RAFTERS
LATERAL BRACING
OSB SHEATHING
ROOF-TYPE:
HIP
COMPLEX
CROSSED GABLE
ATTIC ACCESS:
HATCH
METHOD USED TO OBSERVE ATTIC:
FROM ENTRY
CRAWLSPACE ACCESS:
NO CRAWLSPACE
METHOD USED TO OBSERVE CRAWLSPACE:
NO CRAWLSPACE
Inspection Items
1.0 FOUNDATION - Inspect and Describe
Comments: Inspected
Foundation was poured concrete.  It extends to a basement area, on the north side of the property, a centrally running footing that runs east to west and a poured concrete slab under the garage area to the south.

Foundation displayed only minor signs of cracking and spalling (Picture 1) along the exterior and is not equipped with flashing.  There are weep holes located at intervals around the structure in the bottom, vertical butt brick joints.  They appear to be generally clean and unclogged.

The interior of the foundation, as observed in the furnace and utility rooms, displayed only minor signs of small cracks, consistent with the structure's age, with no bulging or efflorescence.  There were no signs of past water infiltration.

The sill plate is solid, with no signs of rot and only minor, old staining.

The grade around the foundation is above the recommended minimum of 6" below the top at the north (Picture 2) and west (Picture 3, 4) sides of the property.  This can lead to water infiltration.



1.0 Picture 1

1.0 Picture 2

1.0 Picture 3

1.0 Picture 4
1.1 FOUNDATION - Findings
Comments: Inspected, Repair or Replace
1) RR - Recommend that the grade around the entire perimeter of the property be lowered to keep a minimum of 6" (for brick exterior houses) and 8" for siding or stucco exterior houses) of the foundation exposed to guard against water infiltration into the structure.
1.2 WALLS - Inspect and Describe
Comments: Inspected
Structural walls are 2 x 4 studs.  Where able to be observed, they are without major staining, twist or physical damage.  The sill plates, where able to be observed, was solid, displaying no signs of rot and only minor signs of past water staining.  Moisture readings were well within allowable limits (under 6%).

There is a small area, located in the northwest corner of the garage, where there is evidence of slight past water staining (Picture 1), but measurements taken for moisture were below 6%.  See Roofing and Attic Structure section for more information.



1.2 Picture 1
1.3 BEAMS, COLUMNS OR PIERS - Inspect and Describe
Comments: Inspected
There is a steel girder, running north to south under the center of the structure.  It is covered for most of its length, but appears to be free of rust and physical damage.

This girder is supported by galvanized metal posts, which, where observable, are properly attached, hang plumb and display no signs of rust or physical damage.  The placement of the supporting post at the southern end, in the utility room (Picture 1), appears to be supported on the middle foundation support by metal shims.  While this is not an entirely proper construction technique, it appears to be sufficient and displays no signs of shifting, displacement or movement.



1.3 Picture 1
1.4 FLOORS - Inspect and Describe
Comments: Inspected
Structural floor members are 2 x 8 wooden joists, were observed.  They display no signs of warp, staining or physical damage, are equipped with limited cross bracing and have only minor notches.

The floor joists are covered with 3/4" plywood which was not able to be fully inspected because it was covered, but demonstrates no signs of sag or softness.

1.5 CEILINGS - Inspect and Describe
Comments: Inspected
Ceiling structure, where observed, was 2 x 8 wooden joists that displayed no signs of staining, rot or physical damage.
1.6 ROOF STRUCTURE AND ATTIC - Inspect and Describe
Comments: Inspected
Roof structure was observed from the garage (southern gable) and from the hatch (central hip).  The northern gable roof had a cathedral ceiling in most of its area and the hatch to the limited attic in the northern gable was in a closet in the kitchen was obstructed.

The attic and roof structure is stick built, with 2 x 6 rafters.  The southern gable is equipped with 2 x 4 collar tiles, a 2 x 8 ridge board, 2 x 4 extension from gable end to ridgeboard and 2 x 10 spreaders.  The roof is sheathed with OSB and displays no signs of staining with the exception of a small area, located in the northwest corner of the garage where there is evidence of past water infiltration from an improperly installed downspout on the roof above (Picture 1).  This is accompanied by signs of old water staining in the adjacent 2 x 4 wall studs and headers.  Moisture readings are below 6%.  There is some softness in the black area of the roof sheathing.

The hip roof is 2 x 6 wooden rafters, supported by 2 x 4 posts and a 2 x 8 ridgeboard (Picture 2) and 2 x 4 collar ties.  There are no signs of water staining or physical damage on the OSB roof sheathing.



1.6 Picture 1

1.6 Picture 2
1.7 ROOF STRUCTURE AND ATTIC - Findings
Comments: Inspected, Repair or Replace
1) RR - Recommend that the water damaged OSB roof sheathing, located in the garage, northwest corner, be evaluated and repaired, along with the repair of the downspouts on the western side of the garage gable roof, proximate to the hip roof side, as needed, by a licensed and insured roofer.



Exterior

The home inspector shall observe: Wall cladding, flashings, and trim; Entryway doors and a representative number of windows; Garage door operators; Decks, balconies, stoops, steps, areaways, porches and applicable railings; Eaves, soffits, and fascias; and Vegetation, grading, drainage, driveways, patios, walkways, and retaining walls with respect to their effect on the condition of the building. The home inspector shall: Describe wall cladding materials; Operate all entryway doors and a representative number of windows; Operate garage doors manually or by using permanently installed controls for any garage door operator; Report whether or not any garage door operator will automatically reverse or stop when meeting reasonable resistance during closing; and Probe exterior wood components where deterioration is suspected. The home inspector is not required to observe: Storm windows, storm doors, screening, shutters, awnings, and similar seasonal accessories; Fences; Presence of safety glazing in doors and windows; Garage door operator remote control transmitters; Geological conditions; Soil conditions; Recreational facilities (including spas, saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities); Detached buildings or structures; or Presence or condition of buried fuel storage tanks. The home inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris that obstructs access or visibility.

Styles & Materials
SIDING STYLE:
BEVEL
BRICK
VERTICAL WOOD SIDING
SIDING MATERIAL:
FULL BRICK
METAL
VERTICAL WOOD SIDING
EXTERIOR ENTRY DOORS:
FIBERGLASS
INSULATED COMPOSITE
APPURTENANCE:
SIDEWALK
DECK
POURED CONCRETE SLAB PORCH
GARAGE DOOR MATERIAL:
COMPRESSED BOARD
GARAGE DOOR TYPE:
THREE AUTOMATIC
DRIVEWAY:
ASPHALT
Inspection Items
2.0 WALL CLADDING FLASHING AND TRIM - Inspect and Describe
Comments: Inspected
Exterior walls are a mixture of brick on the lower half of the house, vertically oriented wooden siding on the upper portion and metal siding on the south and west sides of the garage and the north side of the house.

The brick exterior displays no significant signs of cracking or mortar loss.  There are areas, where the brick meets the metal siding (Picture 1) or the roof soffits (Picture 2), around windows where the caulk is cracked.  This is normal and caulk requires annual examination and repair.

The wooden siding displays no signs of rot, water staining or physical damage.  There area some areas where the siding is slightly separated from the wall (Picture 4) and minor nail pops  There is also an area, below the 2nd floor level windows on the front of the property, where the siding appears to be slight twisting under the windows..  There is also an area, located on the southeast corner of the central house area, where some wooden trim needs to be patched and re-painted (Picture 3).



2.0 Picture 1

2.0 Picture 2

2.0 Picture 3

2.0 Picture 4
2.1 WALL CLADDING FLASHING AND TRIM - Findings
Comments: Inspected, Watch List - Maintenance
1) WL - Recommend that exterior caulking, where two different exterior surfaces meet, around windows and doors and where slab porches meet exterior walls, be evaluated and repaired on an annual basis.  This is a regular maintenance item.

2) Wooden siding requires annual evaluation and minor repair of nail pops and flaws.  This is a normal maintenance item.

2.2 DOORS (Exterior) - Inspect and Describe
Comments: Inspected
Front exterior doors areas composite, with glass windows double doors.  They hangs plumb and articulate properly with their latches.  There is some grease like material at the base of the northern door.

The side door, which opens into the garage, is composite and also hangs plumb (Picture 1).  This door should be equipped with spring hinges so as to close automatically and properly separate the living area from the garage as a guard against fire infiltration.

The back door out of the garage (Picture 2) is composite.  Its framing displays signs of cracking and should be painted. 



2.2 Picture 1

2.2 Picture 2
2.3 DOORS (Exterior) - Findings
Comments: Inspected, Repair or Replace, Significantly Deficent
1) SD) Recommend that the exterior door between the garage and the living area be equipped with self closing spring type hinges to guard against infiltration or fire or noxious gasses from the garage to the living area.  This is a safety hazard.

2) RR - Recommend scraping, priming and painting of the door frame for the rear garage door.

2.4 WINDOWS (Exterior) - Inspect and Describe
Comments: Inspected
Exterior windows are a mixture of bow and casements.  The exterior frames are wood and display signs of flaking paint (Picture 1).  Exterior wooden window frames should be evaluated annually and re-caulked, scraped, primed and painted as needed to guard against deterioration.

There are areas where the window frames should be re-caulked.

The wooden window frame under the front bow window displays advanced deterioration, but moisture readings are within normal limits and there was no signs of softness in the wood.



2.4 Picture 1
2.5 WINDOWS (Exterior) - Findings
Comments: Inspected, Repair or Replace
1) RR - Recommend exterior wooden window frames be scrapped, primed and re-painted to avoid further deterioration.

2) RR - Recommend that the junction of the window metal cladding and the exterior brick be caulked to prevent water penetration.

2.6 GARAGE DOOR OPERATORS - Inspect and Describe
Comments: Inspected
All three garage doors were tested, with regards to both safety auto-reverse features, and operated properly.  The southmost garage door needs some adjustment of the resistance auto reverse feature.

The bases of the garage doors are beginning to show wear due to water infiltration (Picture 1).

The springs and cables serving the garage doors are not properly adjusted.



2.6 Picture 1
2.7 GARAGE DOOR OPERATORS - Findings
Comments: Inspected, Watch List - Maintenance, Repair or Replace
1) WL - Adjust resistance auto reverse feature on south garage door.

2) RR - Recommend that garage doors be scrapped, primed and painted.

3) WL - Recommend evaluation and adjustment of the overhead springs and cables for the garage doors.

2.8 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES AND APPLICABLE RAILINGS - Inspect and Describe
Comments: Inspected
The rear deck appear to be solid, but the required concrete footings could not be inspected as they may be below grade.  The south and north steps on the deck moved and had improper footings (Picture 1, 3).  The ballaster railing openings were too wide and pose a safety hazard (Picture 2).  Because of the improper footing on the steps, the south railing is loose.

The front porch is a poured slab and appears to be in serviceable condition.  There is a slight cracking between it an the brick exterior and should be caulked.

The master bedroom is equipped with a wooden balcony outside a set of sliding glass doors.  This balcony has a significant amount of wood rot in its supporting joists (Picture 4, 5).  



2.8 Picture 1

2.8 Picture 2

2.8 Picture 3

2.8 Picture 4

2.8 Picture 5
2.9 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES AND APPLICABLE RAILINGS - Findings
Comments: Inspected, Watch List - Maintenance, Repair or Replace
1) WL - Cracks between poured slab porches and exterior walls should be regularly checked and re-caulked, as needed, to guard against water infiltration.

2) RR - Wooden porches and decks should be supported by the required concrete footings.  All deck and porch steps should also be properly supported by concrete footings.  Recommend evaluation by a licensed and insured deck contractor.

3) SD - All deck railing ballaster should be spaced no further apart than 3 1/2" to guard against entanglement.  This is a safety hazard.

4) SD - Recommend evaluation of the master bedroom balcony by a licensed and insured general contractor.  It is the opinion of this inspector that it is not safe for use.

2.10 EAVES, SOFFITS AND FASCIAS - Inspect and Describe
Comments: Inspected
Soffits and fascia are wood and display no signs of rot, staining or physical damage.  The soffits are equipped with soffits vents for attic ventilation.

The fascia board, located at the peak of the south gable (Picture 1) is slightly misaligned and should be re-nailed to guard against water infiltration.



2.10 Picture 1
2.11 EAVES, SOFFITS AND FASCIAS - Findings
Comments: Inspected, Repair or Replace
1) RR - Recommend securing the fascia board on the gable peak of the south roof.
2.12 VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIOS, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building) - Inspect and Describe
Comments: Inspected
Draining and slope of grade are, in general, good.  There are areas, to the north and west sides, where grade is overly high and should be re-graded.

There are some small trees that are growing right up against the foundation on the south side (Picture 1) that should be removed as a guard against foundation damage.



2.12 Picture 1
2.13 VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIOS, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building) - Findings
Comments: Inspected, Repair or Replace
1) RR - Recommend that the trees growing directly against the foundation on the south side be removed as a guard against foundation damage.



Roofing

The home inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and Signs of' leaks or abnormal condensation on building components. The home inspector shall: Describe the type of roof covering materials; and Report the methods used to observe the roofing. The home inspector is not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems, antennae, and lightning arrestors.

Styles & Materials
ROOF COVERING:
3-TAB FIBERGLASS
DIMENTIONAL
ASPHALT/ FIBERGLASS
VIEWED ROOF COVERING FROM:
GROUND
LADDER
WALKED ROOF
SKY LIGHT (S):
TWO
CHIMNEY (exterior):
BRICK WITH CLAY TILE LINER
Inspection Items
3.0 ROOF COVERINGS - Inspect and Describe
Comments: Inspected
Roof covering is 3 tab asphalt impregnated fiberglass.  The roof covering is in good shape but has a moderate amount of granule loss, especially between the shingle gutters (Picture 1).  There is a small area, located over the garage, where one shingle appears to be damaged (Picture 2), apparently from impact with an object.

3.0 Picture 1

3.0 Picture 2
3.1 ROOF COVERINGS - Findings
Comments: Inspected, Repair or Replace
1) RR - Recommend evaluation of damaged area of roof by a licensed and insured roofer.
3.2 FLASHINGS, SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS - Inspect and Describe
Comments: Inspected
The roof flashings are metal and properly extend under the siding, although the siding is not cut back to the recommended 2" above the roof surface (Picture 1).  There are only minor signs of active water wicking due to this condition.

The chimney, skylights (Picture 3) and vents are properly flashed and there was no sign of water infiltration on the interior.  The chimney is not equipped with a rain cap or a pest screen and it's chimney cap is inadequate and cracked (Picture 2). 



3.2 Picture 1

3.2 Picture 2

3.2 Picture 3
3.3 FLASHINGS, SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS - Findings
Comments: Inspected, Repair or Replace
1) RR - Recommend evaluation of the roof flashing to the wooden sided side walls and the chimney cap by a licensed and insured roofer.
3.4 ROOFING DRAINAGE SYSTEMS - Inspect and Describe
Comments: Inspected
Roof is drained by means of metal gutters and downspouts.  The metal gutters display no signs of rust and only minor signs of physical damage.  The gutter hangers are spaced more than the recommended 18" apart (Picture 1).

The downspouts do not extend far enough away from the foundation to be effective in draining water away from the basement.

There are two downspouts, located on the garage roof and draining the south side of the upper hip roof, that drain directly on the roof and have already cause signs of past water infiltration (Picture 2, 3).



3.4 Picture 1

3.4 Picture 2

3.4 Picture 3
3.5 ROOFING DRAINAGE SYSTEMS - Findings
Comments: Inspected, Repair or Replace
1) RR - Recommend that the downspouts be extended to release drainage water at least 6' away from the structure's foundation.

2) RR - Recommend that all downspouts that drain an upper section of roof terminate either into a lower roof section gutter or to the ground, directly as a guard against excessive water buildup and accelerated roof failure.  Recommend evaluation and repair by a licensed and insured roofer.




Plumbing System

The home inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation; fixtures and faucets; functional flow; leaks; and cross connections; Interior drain, waste, and vent system, including: traps; drain, waste, and vent piping; piping supports and pipe insulation; leaks; and functional drainage; Hot water systems including: water heating equipment; normal operating controls; automatic safety controls; and chimneys, flues, and vents; Fuel storage and distribution systems including: interior fuel storage equipment, supply piping, venting, and supports; leaks; and Sump pumps. The home inspector shall describe: Water supply and distribution piping materials; Drain, waste, and vent piping materials; Water heating equipment; and Location of main water supply shutoff device. The home inspector shall operate all plumbing fixtures, including their faucets and all exterior faucets attached to the house, except where the flow end of the faucet is connected to an appliance. The home inspector is not required to: State the effectiveness of anti-siphon devices; Determine whether water supply and waste disposal systems are public or private; Operate automatic safety controls; Operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning systems; Fire and lawn sprinkler systems; On-site water supply quantity and quality; On-site waste disposal systems; Foundation irrigation systems; Spas, except as to functional flow and functional drainage; Swimming pools; Solar water heating equipment; or Observe the system for proper sizing, design, or use of proper materials.

Styles & Materials
WATER SOURCE:
PUBLIC
WATER FILTERS:
NONE
PLUMBING SUPPLY:
COPPER
PLUMBING DISTRIBUTION:
COPPER
WASHER DRAIN SIZE:
2" DIAMETER
PLUMBING WASTE:
PVC
WATER HEATER POWER SOURCE:
GAS
CAPACITY:
75 GALLON
MANUFACTURER:
RHEEM
Inspection Items
4.0 INTERIOR DRAIN, WASTE AND VENT SYSTEMS - Inspect and Describe
Comments: Inspected
Interior drain waste and vent systems are PVC piping and appear to be serviceable.  All sinks drained properly.  The whirlpool tub in the master bedroom made some excessive gurgling noises on drainage and this may be an indication of inadequate venting.
4.1 INTERIOR DRAIN, WASTE AND VENT SYSTEMS - Findings
Comments: Inspected, Repair or Replace
1) RR - Recommend evaluation the drain venting and noises from the master bathroom whirlpool tub by a licensed and insured plumber.
4.2 INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES - Inspect and Describe
Comments: Inspected
Interior supply pipes are copper and display no signs of corrosion or physical damage.  Water supply and pressure was adequate.

The Whirlpool tun was operated and displayed no signs of pipe mildew.  The whirlpool tun did exhibit gurgling during drainage as detailed in the Drainage Section.

All plumbing fixtures operated properly and appeared sound.  All toilets were properly seated and displayed no signs of leakage and drained properly.

The shower head, located in the hallway bathroom on the 2nd floor was not properly secured in the wall and moves (Picture 1).



4.2 Picture 1
4.3 INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES - Findings
Comments: Inspected, Repair or Replace
1) RR - Recommend installation of a new extunction on the 1st floor bathroom showerhead to guard against showerhead movement.
4.4 HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS - Inspect and Describe
Comments: Inspected
Hot waster heater was a 75 gallon gas unit.  It was observed through a heating cycle and had the proper colored flame.  It was draft vented to a dedicated, insulated steel flue pipe.  TPR drainage pipe was proper.  No gas leaks detected.
4.5 MAIN WATER AND FUEL SHUT-OFF DEVICES (Describe location) - Findings
Comments: Inspected
Main water shut off is located in the furnace utility room on the east wall of the northern basement area (Picture 1).

Main fuel shut off is at the meter, located at the east corner of the north wall (Picture 2).



4.5 Picture 1

4.5 Picture 2
4.6 FUEL STORAGE AND DISTRIBUTION SYSTEMS - Findings
Comments: Inspected
Gas was distributed by means of the proper black pipe.
4.7 SUMP PUMP - Inspect and Describe
Comments: Inspected
There is a drainage sump pump, located at the northwest corner of the basement.  It operated properly.

There is an ejector sump, located in the west portion of the laundry utility room (Picture 1).  It was sealed and could not be tested, although it did go on by itself when the toilet was used.



4.7 Picture 1
4.8 SUMP PUMP - Findings
Comments: Inspected, Significantly Deficent
1) SD - Recommend that all water handling appliances, including sump pumps and water pressure pumps, be GFCI protected.  This is a safety hazard.  Also recommend that all sump pumps be equipped with battery backup so that their operation is assured during periods of electrical blackout. SD - Recommend that all water handling appliances, including sump pumps and water pressure pumps, be GFCI protected.  This is a safety hazard.  Also recommend that all sump pumps be equipped with battery backup so that their operation is assured during periods of electrical blackout.



Electrical System

The home inspector shall observe: Service entrance conductors; Service equipment, grounding equipment, main over current device, and main and distribution panels; Amperage and voltage ratings of the service; Branch circuit conductors, their over current devices, and the compatibility of their ampacities and voltages; The operation of a representative number of installed ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls; The polarity and grounding of all receptacles within six feet of interior plumbing fixtures, and all receptacles in the garage or carport, and on the exterior of inspected structures; The operation of ground fault circuit interrupters; and presence of smoke and carbon monoxide detectors. The home inspector shall describe: Service amperage and voltage; Service entry conductor materials; Service type as being overhead or underground; and Location of main and distribution panels. The home inspector shall report any observed aluminum branch circuit wiring. The home inspector shall report on presence or absence of smoke detectors. The home inspector is not required to: Insert any tool, probe, or testing device inside the panels; Test or operate any over current device except ground fault circuit interrupters; Dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels; or Observe: Low voltage systems; Security system devices, heat detectors, or carbon monoxide detectors; Telephone, security, cable TV, intercoms, or other ancillary wiring that is not a part of the primary electrical distribution system; or Built-in vacuum equipment.

Styles & Materials
ELECTRICAL SERVICE CONDUCTORS:
BELOW GROUND (Lateral Drop)
METER CAPACITY:
200 AMPS
PANEL CAPACITY:
200 AMP
PANEL TYPE:
CIRCUIT BREAKERS
ELEC. PANEL MANUFACTURER:
GENERAL ELECTRIC
BRANCH WIRE 15 and 20 AMP:
COPPER
WIRING METHODS:
ROMEX
CONDUIT
Inspection Items
5.0 SERVICE DROP AND ENTRANCE, CONDUCTORS - Inspect and Describe
Comments: Inspected
Service is by lateral drop with the meter located on the west side of the northern end of the property (Picture 1).  Meter is rated for 200 amp service.  No signs of rust of physical damage.

5.0 Picture 1
5.1 SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS - Inspect and Describe
Comments: Inspected
Main equipment service panel is located behind a wall door on the western side of the north basement area.  The main breaker is rated for 200 amps.  The panel appears clean and without signs of rust, although there are some small spider webs inside.  Grounding means is underground and not inspected, but the grounding ware is properly bonded to the panel and the neutral buss in the panel.
5.2 BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE - Inspect and Describe
Comments: Inspected
All branch conductors are solid copper and of the proper size and gauge.  The wiring is neat and the wires display no signs of discoloration or melting of insulation.

There are two double ganged, 240 volt breakers serving the air conditioning compressor and the electric oven.

All wiring distributed from the main panel are in conduit.  There are signs of later electrical additions which was done using unarmored flexible cable (Romex type) which displays no signs of damage and is properly secured.  It is unsure whether this type of wiring is allowed.

5.3 BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE - Findings
Comments: Inspected, Repair or Replace
1) RR - Recommend evaluation of the added wiring, located in the laundry utility room to determine the legality of its use by a licensed and insured electrician.
5.4 CONNECTED DEVICES AND FIXTURES - Inspect and Describe
Comments: Inspected
All switches and outlets tested properly for polarity and grounding.  All switches tested properly.  The exterior outlet, located near the front door was not powered.

The switch serving the in sink disposer operates intermittently and should be replaced (Picture 1).



5.4 Picture 1
5.5 CONNECTED DEVICES AND FIXTURES - Findings
Comments: Inspected, Significantly Deficent
1) RR - Recommend evaluation of the exterior outlet located near the front door by a licensed and insured electrician.  It was not powered.
5.6 GFCI, AFCI PROTECTION OF RECEPTACLES - Inspect and Describe
Comments: Inspected
The garage was equipped with a GFCI outlet that operated properly.  The exterior outlet, located at the rear of the property operated properly.

No GFCI or AFCI outlets were observed in the living area of of the property, nor were their any GFCI or AFCI breakers in the main service equipment panel.  Was not able to inspect the outlet serving the whirlpool tub in the master bathroom because the access panel was not accessible.

5.7 GFCI, AFCI PROTECTION OF RECEPTACLES - Findings
Comments: Inspected, Significantly Deficent
SD - Recommend GFCI (Ground Fault Circuit Interrupt) protected outlets, or GFCI circuit breakers for all outlets that are:
  • Over the counter in kitchens and anywhere in bathrooms.
  • Within 6' or any water source (sinks, bathtubs, bathroom basins)
  • Located in unfinished areas of basements.
  • In garages.
  • Powering garage door openers serving metal garage doors.
  • Serve water carrying appliances, such as dishwashers, in sink disposers, sump pumps, water supply boost pumps, sprinkler systems or clothes washers.
  • Located on the exterior of the house.
  • Around pools, spas or that power whirlpool type tubs.

Recommend  AFCI (Arc Fault Circuit Interrupt) protected outlets or circuit breakers be used for all branch wiring that services bedroom areas.

Recommend that all such installation be done by a licensed and insured electrical contractors and that these outlets and breakers be tested every month by means of the test buttons that they are equipped with.

5.8 SMOKE DETECTORS, CARBON MONOXIDE DETECTORS - Inspect and Describe
Comments: Inspected
Smoke detectors were located in the hallway outside the 2nd floor bedrooms and the basement bedroom.
5.9 SMOKE DETECTORS, CARBON MONOXIDE DETECTORS - Findings
Comments: Inspected, Significantly Deficent
SD) - Recommend that smoke detectors be located:
  • In the hallways outside of bedrooms.
  • At the top and bottom of all stairways.
  • In the kitchen

Recommend that carbon monoxide detectors be located in all bedrooms and in any utility room containing a gas fired water heater, furnace or boiler.

Recommend that all smoke and carbon monoxide detectors be hard wired to the building's electrical system and be equipped with rechargeable battery backup.




Heating

The home inspector shall observe permanently installed heating systems including: Heating equipment; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The home inspector shall describe: Energy source; and Heating equipment and distribution type. The home inspector shall operate the systems using normal operating controls. The home inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The home inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.

Styles & Materials
HEAT TYPE:
FORCED AIR
FORCED DRAFT
FURNACE EFFICENCY:
HIGH EFFICENCY
INSUFFICIENT COMBUSTION AIR
ENERGY SOURCE:
NATURAL GAS
NUMBER OF HEAT SYSTEMS (excluding fireplaces):
ONE
HEAT SYSTEM BRAND:
ULTRA
DUCTWORK:
RECTANGULAR
GALVANIZED STEEL
FILTER TYPE:
ELECTRONIC AIR CLEANER
TYPES OF FIREPLACES:
GAS/LP LOG STARTER
OPERABLE FIREPLACES:
ONE
NUMBER OF WOODSTOVES:
NONE
Inspection Items
6.0 HEATING EQUIPMENT - Inspect and Describe
Comments: Inspected
Furnace was located in the basement utility room on the east wall.  It was a forced draft, high efficiency model manufactured in 1989.  The flame was observed during a heating cycle and has an excessive yellow case.  This could be due to insufficient combustion air and/or the furnace not being regularly maintained.  High efficiency furnaces should be inspected and maintained annually.

There was a vent located in the rerun air duct to the east of the furnace that is probably robbing the furnace of combustion air (Picture 1).



6.0 Picture 1
6.1 HEATING EQUIPMENT - Findings
Comments: Inspected, Significantly Deficent
1) SD - Recommend that the furnace be evaluated by a licensed and insured HVAC contractor to determine if the amount of combustion air is sufficient for proper furnace operation.  This is a safety concern.

2) SD - Recommend that the return duct vent, located to the east of the furnace, be covered over to avoid it robbing the furnace of combustion air.

6.2 NORMAL OPERATING AND SAFETY CONTROLS - Inspect and Describe
Comments: Inspected
The furnace responded properly to the thermostat controls, located on an inside wall in the dining room on the 1st floor, located on the north end of the structure.

The main electrical shut off switch for the furnace blower is located on the west side of the furnace.

6.3 CHIMNEYS, FLUES AND VENTS - Inspect and Describe
Comments: Inspected
The furnace is vented by means of PVC vent pipe to the side of the property, at the front to the north of the front door.  The vent termination is equipped with a metal cover that is damaged (Picture 1).

6.3 Picture 1
6.4 CHIMNEYS, FLUES AND VENTS - Findings
Comments: Inspected, Repair or Replace
1) Recommend that the furnace vent flue be covered with an appropriate vent termination by a licensed and insured HVAC technician.
6.5 HEAT DISTRIBUTION SYSTEMS - Inspect and Describe
Comments: Inspected
Both heat and air conditioning is distributed by means of rectangular and round galvanized steel ductwork that is of sufficient size for both heating and air conditioning service.  It displays only minor signs of rust and ho physical damage.  Closer examination shows that the ductwork has small amounts of debris (Picture 1).

6.5 Picture 1
6.6 HEAT DISTRIBUTION SYSTEMS - Findings
Comments: Inspected, Watch List - Maintenance
1) WL - Recommend that the ductwork be cleaned by a licensed and insured duct cleaning contractor.
6.7 SOLID FUEL HEATING DEVICES - Inspect and Describe
Comments: Inspected
Property is equipped with a single wood burning fireplace located at the southwest corner of the lower level family room.  The fireplace is equipped with a gas log lighter.  The damper operated properly and the flue has minor soot buildup.
6.8 SOLID FUEL HEATING DEVICES - Findings
Comments: Inspected, Watch List - Maintenance
1) WL - Recommend cleaning of the wood burning fireplace flue by a licensed and insured chimney sweep.

.

6.9 GAS/LP FIRELOGS, LOG LIGHTERS AND FIREPLACES - Inspect and Describe
Comments: Inspected
Fireplace was equipped with a gas 'log lighter'.  It's gas shut off valve was located to the left of the fireplace on the wall base.
6.10 GAS/LP FIRELOGS, LOG LIGHTERS AND FIREPLACES - Findings
Comments: Inspected, Significantly Deficent
1) SD - Gas log lighters are not equipped with automatic gas shut off valves or any safety features that will guard against gas infiltration into the house.  Without any safety feature, this inspector considers log lighters to be unsafe, especially in houses with small children.  Recommend evaluation by a licensed and insured fireplace contractor



Central Air Conditioning

The home inspector shall observe: Central air conditioning and permanently installed cooling systems including: Cooling and air handling equipment; and Normal operating controls. Distribution systems including: Fans, pumps, ducts and piping, with associated supports, dampers, insulation, air filters, registers, fan-coil units; and The presence of an installed cooling source in each room. The home inspector shall describe: Energy sources; and Cooling equipment type. The home inspector shall operate the systems using normal operating controls. The home inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance The home inspector is not required to: Observe window air conditioners or operate cooling systems when weather conditions or other circumstances may cause equipment damage.

Styles & Materials
COOLING EQUIPMENT TYPE:
AIR CONDITIONER UNIT
COOLING EQUIPMENT ENERGY SOURCE:
ELECTRICITY
CENTRAL AIR MANUFACTURER:
CARRIER
NUMBER OF A/C UNITS:
ONE
Inspection Items
7.0 COOLING EQUIPMENT- Inspect and Describe
Comments: Inspected
The air conditioner compressor was located at the northwest corner of the property.  It was manufactured in 1989.  It displayed no signs of rust or physical damage.
7.1 NORMAL OPERATING AND SAFETY CONTROLS - Inspect and Describe
Comments: Inspected
Air conditioner operated properly to normal operating controls.  The air conditioner electrical disconnect is located on the side of the house, directly behind the compressor unit.
7.2 DISTRIBUTION SYSTEMS - Inspect and Describe
Comments: Inspected
See Heating section for details of ductwork.



Interiors

The home inspector shall observe: Walls, ceiling, and floors; Steps, stairways, balconies, and railings; Counters and a representative number of installed cabinets; and a representative number of doors and windows. The home inspector shall: Operate a representative number of windows and interior doors; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies, blinds, or other window treatments.

Styles & Materials
CEILING MATERIALS:
SHEETROCK
WALL MATERIAL:
SHEETROCK
FLOOR COVERING(S):
CARPET
HARDWOOD T&G
TILE
INTERIOR DOORS:
HOLLOW CORE
WOOD
WINDOW TYPES:
CASEMENT
WOOD
WINDOW MANUFACTURER:
UNKNOWN
CABINETRY:
WOOD
COUNTERTOP:
LAMINATE
Inspection Items
8.0 CEILINGS - Inspect and Describe
Comments: Inspected
Ceilings were without signs of water staining, sag or drywall joint swell.
8.1 WALLS - Inspect and Describe
Comments: Inspected
Walls were without signs of warp, sag, cracking and stains.
8.2 FLOORS - Inspect and Describe
Comments: Inspected
Floors were hardwood, tongue and groove (with intricate inlays) and tile.

There was minor signs of cracking the the tile floor in the entryway.  The remainder of the floors were covered with carpet and not observable.

There is also an area, located on the south side of the whirlpool tub that should be sealed with caulk.

There is a loose tile, located on the steps leading to the whirlpool tun in the master bedroom (Picture 1).



8.2 Picture